Customization: | Available |
---|---|
Task: | Adjust |
Structure: | Combination |
Still deciding? Get samples of US$ 49/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
<1>. NPEXA-GM31 isolated safety barriers provide power to transmitters in hazardous area, then isolate and transmit current or voltage signal to safe area by detecting the current in circuit.
<2>. They support HART digital signal transmission.
<3>. Input, output and power supply, 3 terminals are galvanically isolated from each other, own the advantages of low power consumption and quick response.
Explosive-proof grade: [Ex ia Ga]IIC |
|
Input |
|
Permissible input signal from hazardous area |
DC current signal |
Input impedance | Approx 75Ω |
Inputresistance | 1KΩ |
Output | |
Output signal | Current: 0(4)mA~20mA; 0mA~10mA; Voltage: 0(1)V~5V; 0V~10V; |
Output load capacity |
0(4)mA~20mA: ≤550Ω; 0mA~10mA: ≤1.1KΩ; |
Distribution output voltage (If needed) |
Open circuit voltage≤26V; Full load 20mA output voltage≥16V; |
Other Parameters | |
Accuracy | ±0.1%F.S. |
Temperature drift | ≤30ppm/ºC |
Response time | ≤2mS |
Power supply | 18~32V DC (Recommend 24V DC) |
Power consumption | 1.3W (24V power supply,20mA single output); 1.8W (24V power supply,20mA double output); |
Insulation resistance | ≥100MΩ (between input-ouput-power) |
EMC | IEC61326-3 |
Ambient Conditions |
Operating temperature range: -20~+60ºC |
Relative humidity: 10%~90%RH (40ºC) | |
Operating atmosphere pressure: 80~106kPa | |
Storage and delivery temperature: -40~+80ºC |
Customer's photos