Customization: | Available |
---|---|
Type: | Differential Pressure Transmitter |
Structure Type: | Monocrystalline Silicon Pressure Sensor Transmitte |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
3051 Monocrystalline Silicon Pressure Sensor Transmitter
How it works:
Based on advanced monocrystalline silicon sensor technology, it is carefully designed by combining advanced single-chip microcomputer technology and sensor digital conversion technology. Core component single chip microcomputer, its powerful function and high-speed computing power to ensure the good quality of the transmitter has a powerful interface operation function, digital meter head can display pressure, percentage and current, and 0 ~ 100% analog indication, key operation can easily complete zero transfer, range setting, damping setting and other basic parameters in the case of no standard pressure source. Greatly convenient site debugging.
Product Details:
1. Pressure Range: -1 ~ 400Bar . Customzied
2. Output Signal : 4-20mA +Hart Default. Supply Rs485 . Contact me for check.
3. Medium Temperature : -20~60
4. Material: 304SS Thread. Low copper aluminum alloy shell. Epoxy coating layer.
5. Connected Thread: M20*1.5 Default. Contact me if you need others.
Key description and use:
Z (zero) S (Full) M (function key)
1. Press the button to unlock
Press Z and S keys at the same time for more than 5 seconds to unlock (LCD screen display: OPEN)
2, key zero
Apply ZERO pressure to the transmitter, press the S key for about 5 seconds, the transmitter output 4.000MA current, complete the zero operation (LCD display: ZERO)
3, button full
Apply full point pressure to the transmitter, press the S key for about 5 seconds, the transmitter output 20.000MA current, complete the full adjustment operation (LCD display: SPAN)
4. Clear PV value to zero
Put the transmitter directly at atmospheric pressure, press the button to unlock, and then press the Z and S keys at the same time for about 5 seconds, you can set the current PV value to 0, (LCD PV=0)
Note: If the current PV value deviates from the 0 value by more than 50%FS, the PV value is invalid
5, screen display setting unit
Kpa, atm, MPa, bar, mbar, pa, psi, mmHO, mmHG, gcm, kgcm