Customization: | Available |
---|---|
Type: | DIN Rail Mount Temperature Transmitter |
Measuring Medium: | Temperature |
Still deciding? Get samples of US$ 25/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
<1>. PT100 temperature transmitter accepts the thermal resistance signal from the site,isolates and transformers it to standard current or voltage signal,then send the standard signal to the control room,PLC DCS and display instrument.
<2>. PT100,Cu50 sensor direct interface,containing linearized long line compensation.4-port isolation,the 2 output routes areisolated from each other.
<3>. DIN T rail independent mounting,terminals pluggable.
<4>. BSR has 3 types,1 in/1 out,1 in/2 out,2 in/2 out,input and output signal can be customized.
Input
|
|
Input Signal
|
PT100,Cu50 and other RTD signals
|
RTD Excitation Voltage
|
2.5V
|
Allowed Line Resistance
|
≤100Ω
|
Output
|
|
Output Signal
|
4-20mA;0-20mA;0-10mA;0-5V;0-10V;1-5V;Customized
|
Output Load Resistance |
RL≤500Ω(output current signal);
|
RL≥1KΩ(output voltage signal);
|
|
Other Parameters
|
|
Power Supply
|
DC24V,±10%;AC85-265V
|
Current Consumption |
≤70mA(1 in 1 out,24V power supply,output 20mA);
|
≤90mA(1 in 2out,24V power supply,output 20mA);
|
|
≤100mA(2 in 2 out,24V power supply,output 20mA);
|
|
Accuracy
|
0.2%F.S.
|
Temperature Drift
|
0.005%F.S./ºC (-20ºC~+55ºC)
|
Isolation Intensity
|
1500V AC/1min(between input-ouput-power)
|
Insulation Resistance
|
≥100MΩ(between input-ouput-power)
|
Working Temperature & Humidity
|
-20ºC~+55ºC
|
EMC
|
Complies with GB/T 18268(IEC61326-1)
|
Applicable Equipment
|
2-wires or 3-wires RTD
|