<1>. PA-22 frequency transducer,it isolates frequency signals in the industrial field,
and transformers them into 4-20mA or 0-5V standard signals.
<2>. Standard 35mm DIN rail independent mounting.
Input
|
Frequency range
|
0.1Hz~100KHz
|
Pulse width
|
≥10us
|
|
Level
|
VL≤1V;4V≤VH≤12V(customizable)
|
|
|
Output signal
|
4-20mA;0-20mA;0-5V;0-10V etc
|
Output load resistance
|
RL≤500Ω(output current signal)
RL≥10KΩ(output voltage signal) |
|
|
Power supply
|
DC24V,±10%/AC85-265V
|
Current consumption
|
≤50mA(1 in 1 out,DC24V power supply, output 20mA)
≤70mA(1 in 2 out,DC24V power supply, output 20mA) ≤80mA(2 in 2 out,DC24V power supply, output 20mA) |
|
Accuracy
|
0.1% F.S
|
|
Response time
|
≤1S(0-90%)(TYP)
|
|
Temperature drift
|
0.005%F.S./ºC (-20ºC~+55ºC)
|
|
Isolation intensity
|
1500V AC/1min(between input-ouput-power)
|
|
Insulation resistance
|
≥100MΩ(between input-ouput-power)
|
|
Working temperature range
|
-20ºC~+55ºC
|
|
|
EMC
|
complies with GB/T 18268(IEC61326-1)
|