Customization: | Available |
---|---|
Task: | Adjust |
Structure: | Combination |
Still deciding? Get samples of US$ 49/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
<1>. NPEXB-GM31 isolated safety barrier transmits current signals from safe area to hazardous area by isolating and transmitting current or voltage signals.
<2>. It can control electric transducer,valve positioner and other field apparatus.
<3>. Input, output and power supply, 3 terminals are galvanically isolated from each other, own the advantages of low power consumption and quick response.
Explosive-proof grade: [Ex ia Ga]IIC |
|
Input |
|
Permissible input signal from safe area |
DC current signal Specific type of signal is detailed at product label |
Input voltage drop | < 1.2V |
Output | |
Output signal to hazardous area | Current: 0(4)mA~20mA; 0mA~10mA; Voltage: 0(1)V~5V; 0V~10V; |
Output load capacity |
0(4)mA~20mA: ≤800Ω; 0mA~10mA: ≤1.6KΩ; |
Other Parameters | |
Accuracy | ±0.1%F.S. |
Temperature drift | <40ppm/ºC |
Response time | ≤2mS |
Power supply | 18~32V DC (Recommend 24V DC) |
Power consumption | 1.0W (24V power supply,20mA single output); 1.7W (24V power supply,20mA double output); |
Dielectric strength: (1mA leakage current, 1 minute test time) | ≥3000V AC (between Intrinsic safe and Non intrinsic safe) ≥1500V AC (between Non intrinsic safe and Non intrinsic safe) |
Insulation resistance | ≥100MΩ (between input-ouput-power) |
EMC | IEC61326-3 |
Ambient Conditions |
Operating temperature range: -20~+60ºC |
Relative humidity: 10%~90%RH (40ºC) | |
Operating atmosphere pressure: 80~106kPa | |
Storage and delivery temperature: -40~+80ºC |
Parameters certified by China National Quality Supervision and Test Centre for Explosion Protected Electrical Products (CQST)
Um =250V AC/DC; Between terminal 1 & 2, 3 & 4; Uo=28V, Io=93mA, Po=651mW
IIC | IIB | IIA | |
Co | 0.087μF | 0.68μF | 2.27μF |
Lo | 4mH | 12mH | 32mH |
Customer's photos